GMV5 D.C INVERTER MULTI VRF SERVICE MANUAL
136
If no exception is detected, the main board is displayed as follows and the unit automatically enters
the next commissioning step.
Progress
Commissioning Code
Progress Code
Status Code
Meaning
LED1
LED2
LED3
Code
Display
Status
Code
Display
Status
Code
Display
Status
06_Component
detection for ODU
db
On
06
On
OC
On
The system detects
that no ODU
component fails and
automatically enters
the next step.
If an exception is detected, the unit retains the current status and waits for manual troubleshooting.
Corresponding faults include:
Progress
Commissioning Code
Progress Code
Status Code
Meaning
LED1
LED2
LED3
Code
Display
Status
Code
Display
Status
Code
Display
Status
06_Component
detection for ODU
db
On
06
On
Corresp
onding
fault
code
On
The system detects
component failure of
ODU.
For details about the above troubleshooting method, refer to the "Troubleshooting Method" part.
Step 11: Unit commissioning step 07 is component detection for IDU.
If no exception is detected, the main board is displayed as follows and the unit automatically enters
the next commissioning step.
Progress
Commissioning
Code
Progress Code
Status Code
Meaning
LED1
LED2
LED3
Code
Display
Status
Code
Display
Status
Code
Display
Status
07_Component
detection for IDU
db
On
07
On
OC
On
The system detects that
no IDU component fails
and automatically enters
the next step.
If an exception is detected, the unit retains the current status and waits for manual troubleshooting.
Corresponding faults include: