GMV5 D.C INVERTER MULTI VRF SERVICE MANUAL
206
NOTE:
You can infer from the preceding figures the current of the compressor operating at other
frequency bands.
Step 2:
Check whether the compressor sounds sharp or rubs. Compare the sound of the faulty compressor
with that of normal ones.
Step 3:
Check whether the electric expansion valves of ODUs and the 4-way valves act, and whether the oil
return pipes and oil balance valves 1 and 2 are normal. Touch the pipelines next to the return capillary
tubes to check whether there is oil flowing.
Check method for each part:
1) Electric expansion valve: This valve will reset for each power-on or power-off action. Touch the
valve and you will feel its vibration during the reset action. A crack sound will be heard as well.
Electric expansion
valve of heater
Electric
expansion valve
of subcooler