GMV5 D.C INVERTER MULTI VRF SERVICE MANUAL
216
3) Check gas/liquid separator.
After the gas separator is taken out, check whether it contains impurities. The check procedure is as
follows:
Use a glass container to hold the liquid. Check liquid impurities and colours and block the container
for further factory inspection.
NOTE:
If the compressor needs replacement, the gas/liquid separator needs replacement as well,
regardless whether the separator contains impurities or has faults or not.
3. Remove the
gas/liquid separator
1. Weld the
inlet and outlet
pipes of the
gas separator
2. Unscrew the
gas separator
This angle should
not exceed 20°.
NOTE: While drawing
liquid out from the gas
separator, make sure to
keep the outlet downward.