Step 7: Preparations.
1) Prepare new parts.
In the course of moving compressors, do not lay them down or put them upside down. The tilt angle
should be less than 30°. Make sure oil will not overflow from the oil balance opening. The inlet and outlet
should be blocked. If the sealing rubber is not available, cover them with tape to prevent direct contact of
oil and air.
NOTE:
The new compressor must be consistent with the faulty one in model.
Check the rubbers for oil separator, gas separator, oil balancer, and drying filter. If they are lost
during transportation, cover the parts with tape to keep the compressor dry and airtight inside.
The rubbers
used for
blocking the
inlet and outlet
of compressors
must be intact
The cover of the
electric box
should be intact