GMV5 D.C INVERTER MULTI VRF SERVICE MANUAL
20
7.2 Each ODU system can be connected to multiple IDUs. Detailed
information about the number of units to be connected and capacity
ranges is shown in the following table:
Maximum Number of
Connected IDUs (units)
Capacity Range of Connected IDU
(kBtu/h)
During installation, please strictly follow the above capacity range and number to construct,
otherwise, units may work abnormally and compressors may even be damaged