GMV5 D.C INVERTER MULTI VRF SERVICE MANUAL
20
7.2 Each ODU system can be connected to multiple IDUs. Detailed
information about the number of units to be connected and capacity
ranges is shown in the following table:
Model
Maximum Number of
Connected IDUs (units)
Capacity Range of Connected IDU
(kBtu/h)
Minimum Capacity
Maximum Capacity
GMV-72WM/B-F(U)
12
36.0
97.2
GMV-96WM/B-F(U)
16
48.0
129.6
GMV-120WM/B-F(U)
20
60.0
162.0
GMV-144WM/B-F(U)
25
72.0
194.4
GMV-168WM/B-F(U)
29
84.0
226.8
GMV-192WM/B-F(U)
33
96.0
259.2
GMV-216WM/B-F(U)
37
108.0
291.6
GMV-240WM/B-F(U)
41
120.0
324.0
GMV-264WM/B-F(U)
45
132.0
356.4
GMV-288WM/B-F(U)
49
144.0
388.8
GMV-312WM/B-F(U)
53
156.0
421.2
GMV-336WM/B-F(U)
58
168.0
453.6
GMV-360WM/B-F(U)
61
180.0
486.0
During installation, please strictly follow the above capacity range and number to construct,
otherwise, units may work abnormally and compressors may even be damaged

Table of Contents

Other manuals for Gree GMV-120WM/B-F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-120WM/B-F and is the answer not in the manual?

Gree GMV-120WM/B-F Specifications

General IconGeneral
BrandGree
ModelGMV-120WM/B-F
CategoryInverter
LanguageEnglish

Related product manuals