GMV5 D.C INVERTER MULTI VRF SERVICE MANUAL
364
Possible cause:
Communication between the server and gateway fails.
Solution:
(1) Check whether a hardware fault exists. Check gateway running. For details, refer to section 7.1
"Hardware Faults".
(2) If there is not hardware fault or the fault is addressed, restart BAS Service. There are two
methods to restart BAS Service.
Method a.
①
Right click the BAS Manager icon in the status bar at the lower right corner on the desktop and
choose ―Open‖.
②
In the displayed ―BAS Manager‖ window, click ―Start‖ to enable BAS Manager.
Method b.