DC Inverter Multi VRF System User Manual
23
temp is, the smaller temp difference is. If
ambient temp is 25~35 ℃ in cool mode,
system’s high pressure value will be within
44~53℃.
●In heat mode, if ambient temp is above -5℃,
system’s high pressure value is within 40~52℃.
If ambient temp is low and many IDUs are
turned on, the high pressure will be lower.
●When ambient temp in cool mode is 25~35℃,
the low pressure value is 0~8℃.
●When ambient temp in heat mode is above
-5℃, the low pressure value is -15~8℃.
Opening angle of
thermal EXV
●In cool mode, the thermal electronic
expansion valve remains 480PLS.
●In heat mode, the adjustable opening angle of
EXV is 40~480PLS.
Compressor’s
operating freq
Compressor’s
operating current
When compressor works normally, the current
is no more than 18.4A.
When ambient temp is below 35℃, IPM temp is
lower than 80℃ and the highest temp won’t be
above 95℃.
Fan motor’s
operating freq
Changes in 0~49Hz according to system’s
pressure.
Indoor heat
exchanger’s inlet
temp
●According to ambient temp, for a same IDU in
cool mode, the inlet temp will be 1℃~7℃ lower
than the outlet temp, and 4~9℃ higher than the
low pressure value.
●For a same IDU in heat mode, the inlet temp
will be 10℃~20℃ lower than the outlet temp.
Indoor heat
exchanger’s inlet
temp
Opening angle of
indoor EXV
●In cool mode, the opening angle of indoor EXV
varies within 70~480PLS.
●In heat mode, the opening angle of indoor
EXV varies within 70~480PLS.
Number of IDUs detected by software is the
same with the actual number. No
communication error.
Indoor unit can drain water out completely and
smoothly. Condensate pipe has no backward
slope of water; Water of outdoor unit can be
drained completely through drainage pipe. No
water drop from unit base.
Compressor and indoor/outdoor fan motor do
not have strange noise. Unit can operate
normally.
6 Common Malfunctions and Troubleshooting
Warning:
①
If there is abnormal condition (e.g. unpleasant smell), turn unit off and disconnect power
immediately. Then contact Gree authorized service center. If unit continues operation
despite the abnormal condition, it may get damaged and lead to electric shock or fire
hazard.
②
Do not repair the air conditioner by yourself. Improper maintenance may lead electric
shock or fire hazard. Please contact Gree authorized service center for maintenance.
●Please check the items below before calling for maintenance.