EasyManua.ls Logo

Gree GMV-24WL/C-T

Gree GMV-24WL/C-T
150 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GREE DC Inverter Side Discharge VRF for North America
123
Removal operation of gas liquid separator
Remark: Before removing the gas liquid separator, please make sure that there’s no refrigerant inside the pipeline of
system and disconnect the power
Process
Photo
Operation Instruction
1.Disconnect
inlet pipe and
exit pipe of gas
liquid separator
● Weld those two
connection spots on
the gas liquid
separator and then
pull out the
connection pipe
Note: During welding
process, do not let
flame burn out other
parts
2. Replace gas
liquid separator
● Loose 4 screws
with screwdriver
● Replace gas lliquid
separator
3. Replace
gas liquid
separator
● Weld the pipe
connected with gas
liquid separator
● Fix the screws at
the base of gas liquid
separator well again
Note: During welding
process, do not let
flame burn out other
parts

Table of Contents

Other manuals for Gree GMV-24WL/C-T

Related product manuals