GREE DC Inverter Side Discharge VRF for North America
72
5.2 Dimension of Pipe (Main Pipe) from ODU to the 1st Indoor
Branch
Dimension of pipe from ODU to the 1st indoor branch will be determined by the dimension of
outdoor connection pipe.
Fig.6
Dimension of outdoor connection pipe:
Basic module
Pipe dimension
Gas pipe
(mm/inch)
Liquid pipe
(mm/inch)
GMV-24WL/C-T(U)
Φ15.9
(Φ5/8)
Φ9.52
(Φ3/8)
GMV-28WL/C-T(U)
Φ15.9
(Φ5/8)
Φ9.52
(Φ3/8)
GMV-36WL/A-T(U)
GMV-36WL/C-T(U)
Φ15.9
(Φ5/8)
Φ9.52
(Φ3/8)
GMV-48WL/A-T(U)
GMV-48WL/C-T(U)
Φ15.9
(Φ5/8)
Φ9.52
(Φ3/8)
GMV-60WL/A-T(U)
GMV-60WL/C-T(U)
Φ19.05
3/4)
Φ9.52
(Φ3/8)