GREE DC Inverter Side Discharge VRF for North America
94
No.
Debug item
Parameter
name
Unit
Reference
12
GMV-60WL/A-T(U)
GMV-60WL/C-T(U)
Changes in
0~40Hz according
to system’s
pressure.
13
IDU
paramet
ers
IDU ambient
temp
()
-
14
Indoor heat
exchanger’s
inlet temp
()
According to ambient temp, for a same IDU in cool mode,
the inlet temp will be 1~7(34~45) lower than the outlet
temp, and 4~9(39~48) higher than the low pressure
value.
For a same IDU in heat mode, the inlet temp will be 10
~20(50~68) lower than the outlet temp.
15
Opening angle
of indoor EXV
PLS
GMV-24WL/C-T(U)
GMV-28WL/C-T(U)
In cool mode, the
opening angle of
indoor EXV varies
within 70~480PLS.
In heat mode, the
opening angle of
indoor EXV varies
within 70~480PLS.
16
GMV-36WL/A-T(U)
GMV-48WL/A-T(U)
GMV-36WL/C-T(U)
GMV-48WL/C-T(U)
In cool mode, the
opening angle of
indoor EXV varies
within 70~480PLS.
In heat mode, the
opening angle of
indoor EXV varies
within 70~480PLS.
17
GMV-60WL/A-T(U)
GMV-60WL/C-T(U)
In cool mode, the
opening angle of
indoor EXV varies
within 70~480PLS.
In heat mode, the
opening angle of
indoor EXV varies
within 40~480PLS.
18
Communication
parameters
Communicatio
n data
-
Number of IDUs detected by software is the same with the
actual number. No communication error.
19
Drainage system
-
-
Indoor unit can drain water out completely and smoothly.
Condensate pipe has no backward slope of water; Water of
outdoor unit can be drained completely through drainage
pipe. No water drop from unit base.
20
Others
-
-
Compressor and indoor/outdoor fan motor do not have
strange noise. Unit can operate normally.