GREE DC Inverter Side Discharge VRF Ⅱ for North America
94
GMV-60WL/A-T(U)
GMV-60WL/C-T(U)
Changes in
0~40Hz according
to system’s
pressure.
Indoor heat
exchanger’s
inlet temp
According to ambient temp, for a same IDU in cool mode,
the inlet temp will be 1℃~7℃(34~45℉) lower than the outlet
temp, and 4~9℃(39~48℉) higher than the low pressure
value.
For a same IDU in heat mode, the inlet temp will be 10℃
~20℃(50~68℉) lower than the outlet temp.
Opening angle
of indoor EXV
GMV-24WL/C-T(U)
GMV-28WL/C-T(U)
In cool mode, the
opening angle of
indoor EXV varies
within 70~480PLS.
In heat mode, the
opening angle of
indoor EXV varies
within 70~480PLS.
GMV-36WL/A-T(U)
GMV-48WL/A-T(U)
GMV-36WL/C-T(U)
GMV-48WL/C-T(U)
In cool mode, the
opening angle of
indoor EXV varies
within 70~480PLS.
In heat mode, the
opening angle of
indoor EXV varies
within 70~480PLS.
GMV-60WL/A-T(U)
GMV-60WL/C-T(U)
In cool mode, the
opening angle of
indoor EXV varies
within 70~480PLS.
In heat mode, the
opening angle of
indoor EXV varies
within 40~480PLS.
Number of IDUs detected by software is the same with the
actual number. No communication error.
Indoor unit can drain water out completely and smoothly.
Condensate pipe has no backward slope of water; Water of
outdoor unit can be drained completely through drainage
pipe. No water drop from unit base.
Compressor and indoor/outdoor fan motor do not have
strange noise. Unit can operate normally.