GREE Multi Variable Air Conditioners Indoor Unit
63
4.1.4 User Parameter Query
User parameters can be queried in power-on or power-off status.
(1) Press and hold the “FUNCTION” button for five seconds to enter the user parameter query
interface. The temperature area displays “C00” and “View” is on.
(2) Select a parameter code by pressing “ ” or “ ”.
(3) Press the “ENTER/CANCEL” button to return to the upper-level menu till quitting parameter
query.
The user parameter query list is as follows:
Table 4.1 User Parameter Query List
Display mode:
Timer area: displays the project number of the current IDU.
NOTICE! If the current HBS network consists of multiple
IDUs, only the IDU that has the minimum project number is
displayed.
Project number
query of IDU and
faulty IDU location
1-255: project
number of
online IDU
Operation method:
In “C01” status, press the “MODE” button to enter project
number query of IDU. Press “▲” or “▼” to switch the IDU SN.
Display mode:
Temperature area: displays the fault of the current IDU (in the
case of multiple faults, they are circularly displayed every three
seconds).
Timer area: displays (project number conflict C5 fault)/project
number of the current IDU (project numbers are arranged from
small to large).
Special operations:
After users press the “MODE” button to enter project number
query, the buzzer of the IDU operated by the wired controller
will ring till users quit "C01" query or switch to the next IDU.
Indoor unit quantity
query in the system
network
Timer area: displays the number of IDUs in the system
network.
Preferential
operation query
00: common
operation
01: preferential
operation
Operation method:
In “C06” status, press the “MODE” button to enter the
preferential operation query interface. Press “ ” or “ ” to
switch the IDU SN.
Display mode:
Temperature area: displays the project number of the current
IDU.
Timer area: displays the preferential operation setting value of
the current IDU.
Indoor environment
temperature query
Operation method:
In “C07” status, press the “MODE” button to enter the indoor
environment temperature query interface. Press " " or " " to
switch the IDU SN.
Display mode:
Temperature area: displays the project number of the current
IDU.
Timer area: displays the temperature value of the indoor
environment temperature sensor after replenishment.
Prompt time query
for air filter cleaning
Timer area: displays the prompt time for air filter cleaning.
Wired controller
adress query
Timer area: displays the address of the current wired
controller.