EasyManua.ls Logo

Gree GMV-ND07PLS/A-T(U) - Page 91

Gree GMV-ND07PLS/A-T(U)
266 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GREE Multi Variable Air Conditioners Indoor Unit
85
Setting
Code
Setting Content
Setting Value
P20
Indoor environment temperature
value
01: temperature sensor of air return vent
02: temperature sensor of wired controller
03: temperature sensor of air return vent for cooling, dehumidifying,
and air supply; temperature sensor of wired controller for heating
04: temperature sensor of wired controller for cooling, dehumidifying,
and air supply; temperature sensor of air return vent for heating and
automatic mode
P21
Corrected value settings of
environment temperature sensor of
IDU (for cooling, dehumidifying,
and air supply)
-15 to 15
P22
Corrected value settings of
environment temperature sensor of
IDU (for heating)
-15 to 15
P30
Static pressure settings for indoor
fan
Type 1: 03.04.05.06.07
Type 2: 01.02.03.04.05.06.07.08.09
P31
High-ceiling installation settings
00: standard-ceiling installation height
01: high-ceiling installation height
P32
Capacity adjustment function of
IDU
-40% to +40%
P34
Repeating validity for time-point
timing
00: invalid
01: valid
P35
Factory setting recovery for user
functions
00: invalid
01: factory setting recovery
P36
Factory setting recovery for
engineering settings
00: invalid
01: factory setting recovery
P40
Prevention for heat collection
00: disabled
10: 10 seconds
20: 20 seconds
30: 30 seconds
40: 40 seconds
50: 50 seconds
60: 60 seconds
P42
Project number settings of IDU
1-255
P43
Preferential operation settings
00: no preferential operation
01: preferential operation
P44
One-key project number setting
query for IDU
00: not displayed
01: displayed
P45
One-key project number reset for
IDU
00: invalid
01: project number reset
P46
Accumulated time clearing for air
filter cleaning
00: not cleared
01: cleared

Table of Contents

Related product manuals