Multi Variable Air Conditioners Ducted Type Indoor Unit
6
Material type
Total length of
communication line
between indoor unit and
Wire size
(mm²)
Material
Standard
Remarks
Light/Ordinary
polyvinyl chloride
sheathed cord.
(60227 IEC 52
/60227 IEC 53)
L≤250
2×0.75~2×1.
25
IEC
60227-5
1) Total length of communication
line can't exceed 250m.
2) The cord shall be Circular cord
(the cores shall be twisted
together).
3) If unit is installed in places with
intense magnetic field or strong
interference, it is necessary to
3.3.2 Select Communication Line for Indoor Unit and Indoor Unit (Outdoor Unit)
Fig.3.3.2
Material Type
Total Length L (m) of
between Indoor Unit
and Indoor (Outdoor)
Wire size
(mm²)
Material
Standard
Remarks
Light/Ordinary
sheathed cord.
(60227 IEC 52
/60227 IEC 53)
L≤1000 ≥2×0.75 IEC 60227-5
1) If the wire diameter is enlarged to 2×1
mm², the total communication line length
can reach 1500 m.
2)
The cord shall be Circular cord (the cores
shall be twisted together).
3) If unit is installed in places with intense
magnetic field or strong interference, it is
necessary to use shielded wire.
3.4 Wiring Requirements
(1) Power Cord Size and Air Switch Capacity
Model Power Cord Size
Air Switch
Capacity
Minimum Sectional
Area of Ground Wire
Minimum Sectional
Area of Power Cord
GMV-ND22~180PHS/B-T
220~240V-1ph-50Hz
6 1.0 1.0