DC Inverter Multi
VRF Service Manual
127
38 GMV-Pdm1065W3/NaB-M 380-415V-3Ph-50Hz 125 32+40+40 35.0 6.0+10.0+10.0
40 GMV-Pdm1130W3/NaB-M 380-415V-3Ph-50Hz 125 32+40+40 35.0 6.0+10.0+10.0
42 GMV-Pdm1180W3/NaB-M 380-415V-3Ph-50Hz 125 32+40+40 35.0 6.0+10.0+10.0
44 GMV-Pdm1235W3/NaB-M 380-415V-3Ph-50Hz 125 40+40+40 35.0 10.0+10.0+10.0
46 GMV-Pdm1300W3/NaB-M 380-415V-3Ph-50Hz 125 40+40+40 35.0 10.0+10.0+10.0
48 GMV-Pdm1350W3/NaB-M 380-415V-3Ph-50Hz 125 40+40+40 35.0 10.0+10.0+10.0
50 GMV-Pdm1405W4/NaB-M 380-415V-3Ph-50Hz 160 32+32+40+40 35.0 6.0+6.0+10.0+10.0
52 GMV-Pdm1456W4/NaB-M 380-415V-3Ph-50Hz 160 32+32+40+40 50.0 6.0+6.0+10.0+10.0
54 GMV-Pdm1512W4/NaB-M 380-415V-3Ph-50Hz 160 32+40+40+40 50.0 6.0+10.0+10.0+10.0
56 GMV-Pdm1570W4/NaB-M 380-415V-3Ph-50Hz 160 32+40+40+40 50.0 6.0+10.0+10.0+10.0
58 GMV-Pdm1650W4/NaB-M 380-415V-3Ph-50Hz 160 32+40+40+40 50.0 6.0+10.0+10.0+10.0
60 GMV-Pdm1700W4/NaB-M 380-415V-3Ph-50Hz 160 40+40+40+40 50.0 10.0+10.0+10.0+10.0
62 GMV-Pdm1750W4/NaB-M 380-415V-3Ph-50Hz 160 40+40+40+40 50.0 10.0+10.0+10.0+10.0
64 GMV-Pdm1800W4/NaB-M 380-415V-3Ph-50Hz 160 40+40+40+40 50.0 10.0+10.0+10.0+10.0
7�3 Wiring Sketch Map
7.3.1Wiring Sketch Map between Outdoor Unit
The indoor and outdoor unit is energized separately.
Outdoor unit Outdoor unit Outdoor unit
Max. 4 sets
N21
Electric box Electric box
Electric box
Power
supply
Main
board
Main
board
3N~380V
50Hz
L1 L2 L3 N
L1 L2 L3 N L1 L2 L3 N
L1 L2 L3 N
CN1
QF
Terminal Board
CN18
CN18
Main
board
CN18
CN17
Terminal Board
Terminal Board
Adaptor
board
CN1
Adaptor
board
CN1
Adaptor
board
Communication
wire
Communication
wire
Communication
wire
Communication
wire
To 1 # indoor unit of group 1 To 2 # indoor unit of group 1
To n # indoor unit
of group 1
The part with dotted line is for the on-site wiring of the customer. The power wire diameter and the other specific parameter please
see the installation manual. The mainboard of outdoor units include the module address and transfer address need to confirm at the
work site and dial-up. Each outdoor unit module can connect maximum 16 indoor units, yet need to confirm on the work site. Each
outdoor unit module can connect maximum 16 indoor units as one communication unit.