168
DC Inverter Multi
VRF Service Manual
1�2 Trouble Display of Mainboard LED of Outdoor Unit
Description of indicator LED.
Denition:
LED6:
LED5:
LED4, LED3, LED2, LED1:
Error Description
Main control display of the outdoor units
Transfer
board
Display
Drive board of compressor Drive board of fan motor
LED1 LED2 LED3 LED4 LED5 LED6 Nixietube
LED1
(Red)
LED2
(Yellow)
LED3
(Green)
LED1 (red)
Continous fast
blinking counts
Red Yellow Green
Normal ON
1
Capacity dial-up error
- - - - -
Compressor high-
pressure protection
E1 - - - -
Compressor low-
pressure protection
E3 - - - -
Compressor air-
out protection
E4 - - - -
Overcurrent Protector
E5 - - - -
No-refrigerant protection
E3 - - - -
Error with sub-module
and main control
communication (display
in sub-module)
- - - - -
Communicationerror
with frequency
conversion drive
E5 -
The temperature of
radiating n is too high
E5 -
Radiating n sensor
abnormal
E5 -
Clogged
E5 - - - -
Over-current protection
of frequency conversion
compressor
E5 -
DC input voltage
is too high
E5 -
DC input voltage
is too low
E5 -
IPM ABNORMAL
E5 -
Motor out of
synchronization
E5 -
Overspeed
E5 -
Open phase, tripping E5 -
Temperature drift
protection
E5 -
Error with the temperature
sensor on drive board
E5 -
Startup failure
E5 -
AC current protection
(input side)
E5 - - - -
PFC ABNORMAL
E5 - - - -
Drive module reset
E5 - - - -