DC Inverter Multi
VRF Service Manual
27
CONTROL
Cooling Running
Cooling running
Is startup being initialized
Is compressor
being protected?
Outdoor fan: cooling control mode Outdoor fan: cooling control mode
Outdoor electronic expansion valve:
fully open
Compressor: capacity control
B
Yes
No
Yes
No
4-way valve: stop 4-way valve: stop
4-way valve: stop
Outdoor fan:
protection control
Compressor:
protection control
Compressor: initialized
Outdoor electronic expansion valve:
stop
Outdoor electronic expansion valve:
fully open
Heating running
4-way valve: open
Heating running
Is startup being initialized?
Is defrost running?
Is compressor being
protected?
Outdoor fanheating control mode
Compressorcapacity control
B
Yes
No
Yes
No
Yes
No
Electronic expansion valve of
outdoor unitcapacity control
4-way valve: open
Compressorinitialized
Electronic expansion valve of
outdoor unitcapacity control
4-way valve: reverse
Outdoor fan
defrost control
Compressorinitial defrost control
Electronic expansion valve of
outdoor unitfully open
4-way valve: open
Outdoor fan
protection control mode
Compressorprotection control
Electronic expansion valve of
outdoor unitcapacity control
Outdoor fanheating control mode