DC Inverter Multi
VRF Service Manual
27
CONTROL
Cooling Running
Cooling running
Is startup being initialized ?
Is compressor
being protected?
Outdoor fan: cooling control mode Outdoor fan: cooling control mode
Outdoor electronic expansion valve:
fully open
Compressor: capacity control
B
Yes
No
Yes
No
4-way valve: stop 4-way valve: stop
4-way valve: stop
Outdoor fan:
protection control
Compressor:
protection control
Compressor: initialized
Outdoor electronic expansion valve:
stop
Outdoor electronic expansion valve:
fully open
Heating running
4-way valve: open
Heating running
Is startup being initialized?
Is defrost running?
Is compressor being
protected?
Outdoor fan:heating control mode
Compressor:capacity control
B
Yes
No
Yes
No
Yes
No
Electronic expansion valve of
outdoor unit:capacity control
4-way valve: open
Compressor:initialized
Electronic expansion valve of
outdoor unit:capacity control
4-way valve: reverse
Outdoor fan:
defrost control
Compressor:initial defrost control
Electronic expansion valve of
outdoor unit:fully open
4-way valve: open
Outdoor fan:
protection control mode
Compressor:protection control
Electronic expansion valve of
outdoor unit:capacity control
Outdoor fan:heating control mode