GMV5 Compact Series VRF Outdoor Unit
9
4.2 Piping Design
4.2.1 The Branch of the Connection Pipe
The connection pipe between indoor unit and outdoor unit uses Y type branch, as shown in Fig.5.
线控器
室内机
Y型分歧管
室外机
Fig.5 Schematic diagram of piping connection
4.2.2 Allowable Pipe Length and Drop Height among Indoor and Outdoor Units
Fig.6 Allowable pipe length and drop height among indoor and outdoor units
The equivalent distance of indoor units manifold is 0.5m.
Wired controller
Height difference between outdoor and indoor unit: H
Y-type manifold
Indoor unit
Height difference among indoor units:
h<=15m
Outdoor unit
ODU
IDU
The first
manifold
of indoor
units
IDU
Length of farthest fitting pipe: L120m