26
Outdoor Units_Heat Recovery To n 28 30
Model - GMV-Q336WM/B-U(U) GMV-Q360WM/B-U(U)
Module combination -
GMV-Q96WM/B-U(U)+
GMV-Q120WM/B-U(U)+
GMV-Q120WM/B-U(U)
GMV-Q120WM/B-U(U)+
GMV-Q120WM/B-U(U)+
GMV-Q120WM/B-U(U)
Performance
Nominal Cooling
Capacity
Btu/h 336000 360000
kW 98.5 105.5
Rated Cooling Capacity Btu/h 312000 333000
Nominal Heating
Capacity
Btu/h 378000 405000
kW 110.8 118.7
Rated Heating Capacity Btu/h 352000 378000
Cooling Power Input kW
 
7.30+9.58+9.58
 
9.58+9.58+9.58
Heating Power Input kW
 
7.85+10.42+10.42
 
10.42+10.42+10.42
Sound Pressure Level dB(A) - -
Power Supply - 460V 3~ 60Hz
Compressor
Type - Inverter scroll type Inverter scroll type
Number N 1+2+2 2+2+2
Motor Output
kW - -
Starting Method - Inverter Inverter
Operating Range - - -
Refrigeration Oil Brand - FVC68D or FV-68H FVC68D or FV-68H
Fan
Type×Quantity - Propeller×(2+2+2) Propeller×(2+2+2)
Motor output W 750×2+750×2+750×2 750×2+750×2+750×2
Starting method - Inverter Inverter
Air ow rate
m
3
/h 14000+14000+14000 14000+14000+14000
cfm 8240+8240+8240 8240+8240+8240
Max. external static
pressure
Pa 82 82
in.W.G 0.328 0.328
Ambient
temperature
range
Cooling
°C -5~52 -5~52
23~125.6 23~125.6
Heating
°C -20~24 -20~24
-4~75.2 -4~75.2
Refrigerant
Refrigerant Type - R410A R410A
Refrigerant Charge
Volume
kg 11.2+11.7+11.7 11.7+11.7+11.7
lbs. 25+25.79+25.79 25.79+25.79+25.79
Control - EXV EXV

Other manuals for Gree GMV5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV5 Series and is the answer not in the manual?

Gree GMV5 Series Specifications

General IconGeneral
BrandGree
ModelGMV5 Series
CategoryInverter
LanguageEnglish

Related product manuals