Test Operation & Troubleshooting & Maintenance 
 
hydraulics system pressure according to next item: 
① 
If the pressure is less than 0.5 bar, please recharge the water immediately; 
② 
When recharging, the hydraulics system pressure should be not more than 2.5 Bar. 
5.2 Troubleshooting 
Compressor does 
not start up 
 
  Power supply has problem. 
  Connection wire is loose. 
  Malfunction of mainboard. 
 
Malfunction of compressor.
 
  Phase sequence is reverse. 
  Check out and re-fix. 
  Find out the reasons and repair. 
 
Replace compressor.
 
  Fixing bolt of fan is loose. 
  Fan blade touches shell or grill. 
 
Operation of fan is unreliable.
 
  Re-fix fixing bolt of fan. 
  Find out the reasons and adjust. 
 
Replace fan.
 
Heavy noise of 
compressor
 
  Liquid  slugging  happens  when  liquid 
refrigerant enters into compressor.   
 
Internal parts in compressor are broken. 
 
  Check  if  expansion  valve  is  failure  and 
temp. sensor is loose. If that, repair it. 
 
Replace compressor.
 
Water pump does 
not run or runs 
abnormally
 
  Malfunction of power supply or terminal. 
  Malfunction of relay.   
 
There is air in water pipe.
 
  Find out the reasons and repair.   
  Replace relay. 
 
Evacuate.
 
Compressor starts or 
stops frequently 
 
  Poor or excess refrigerant. 
  Poor circulation of water system. 
 
Low load.
 
  Discharge or add part of refrigerant. 
  Water system is blocked or there is air in 
it. Check water pump, valve and pipeline. 
Clean water filter or evacuate. 
 
Adjust  the  load  or  add  accumulating 
devices. 
 
The unit does not 
heat although 
compressor is 
running
 
  Leakage of refrigerant. 
 
Malfunction of compressor.
 
  Repair  by  leakage  detection  and  add 
refrigerant. 
 
Replace compressor.
 
Poor efficiency of hot 
water heating 
  Poor heat insulation of water system. 
  Poor heat exchange of evaporator. 
  Poor refrigerant of unit.   
  Blockage  of  heat  exchanger  at  water 
side. 
  Enhance heat insulation efficiency of the 
system. 
  Check if air in or out of unit is normal and 
clean evaporator of the unit. 
  Check if refrigerant of unit leaks. 
  Clean or replace heat exchanger.