Unit Control 
 
2.2 Operation Conditions 
Capacities and power inputs are based on the following conditions (floor heating /cooling ) 
Indoor Water Temp 23°C/18°C;                                                                                               
Indoor Water Temp 30°C/35°C;   
Outdoor Air Temp 35°C DB/24°C WB                                                                           
Outdoor Air Temp 7°C DB/6°C WB 
Capacities and power inputs are based on the following conditions (FCU or radiator) 
Indoor Water Temp 12°C/7°C;   
Indoor Water Temp 40°C/45°C;   
Outdoor Air Temp 35°C DB/24°C WB                                                                                             
Outdoor Air Temp 7°C DB/6°C WB 
2.3 Flowchart of Model Selection 
   
2.4 Design Principle 
  Cooling: capacity of the unit ≥ cooling load of the air conditioning 
  Heating: capacity of the unit ≥ max{ heating load, floor heating load, water heating load} 
  Water Tank: it should be selected based on the sanitary outfit or quantity of users. Each unit 
can accommodate only one water tank. 
3 Selection of the Underfloor Coils 
3.1 Calculation of Unit Load for Floor Heating 
Empirical Values of Floor Heating Load Per Square Meter