Unit Control
access to the corresponding setting page.
2. At the
Thermostat
‖ setting page, it can be set to
Air
‖,
Without
‖ or
Air + hot water
‖. When it is
set to ―
Air
‖ or ―
Air + hot water
‖, the unit will run based on the mode set by the thermostat; when it
is set to ―
Without
‖, the unit will run based on the mode set by the control panel.
[Notes]
When ―
Water tank
‖ is set to ―
Without
‖, the ―
Air + hot water
‖ mode is unavailable.
●When ―
Floor debug
‖ and ―
Emergen.mode
‖ have activated, function of the thermostat will be invalid.
●When
Thermostat
is set to
Air
or
Air + hot water
‖, timer function will be disabled and the unit
will run based on the mode set by the thermostat. Meanwhile, mode setting and On/Off operation will
be ineffective.
When ―
Thermostat
‖ is set to ―
Air
‖, the unit will run based on the setting of the thermostat.
When
Thermostat
is set to
Air + hot water
‖, when the thermostat is turned off, the unit can still
perform the
Hot water
mode. In this case, the ON/OFF icon at the homepage does not indicate the
running status of the unit. Running parameters are available at the parameter viewing pages.
When ―
Thermostat
‖ is set to
Air + hot water
‖, operation priority can be set by the control panel (see
Section 2.2.3 and 2.2.4 for more details.)
●The status of the thermostat can be changed only when the unit is turned off.
When it has been activated,
Weekly timer
‖, ―
Clock timer
‖, ―
Temp.timer
‖, and
Preset mode
‖ cannot
be activated at the same time.
●This setting will be memorized upon power failure.
3.2.4.6 Other Thermal
[Operation Instructions]
1. At the commissioning parameter setting page, by touching
Other thermal
‖, the control panel will
access to the corresponding setting page.
2. At the
Other therma
l‖ setting page, ―Other thermal‖ can be set to
With
or
Without
‖,
T-Other
switch on
‖ can be set to the desired value. When ―
Other thermal
‖ is set to ―
With
‖, it is allowed to set
the operating mode for the backup thermal source.
[Notes]
●This setting will be memorized upon power failure.
●There are three working logics for it.
Logic 1
1. The set point of the other thermal should be equal to that of ―WOT-Heat‖.
2. The water pump for other thermal must be always active under the ―Heat‖ mode.
3. Under the
Heat
mode, the 2-way valve will be controlled based on the setting of the control panel.
During heating operation, the water pump of the heat pump unit will be stopped; however, during
standby status, the water pump will start but the other thermal will stop. Under the
Hot water
mode, the