Unit Control 
 
If the outer diameter of the heating pipe is 20mm and thickness is 2mm, then the minimum flow for the 
heating pipe is: 
 
It  can  be  see  that  the  arranged  piping  system  for  the  bathroom  does  not  meet  the  technical 
requirement and must be used in common for the master room. 
7.2.4 Arrangement Design of the Underfloor System for the Master and Bath Rooms 
According to the calculation results, the total heat load for the master and bath rooms is 3196W, heat 
dissipation per unit area is 82W/m
2
, tube spacing of the heating pipe is 300mm, and heat loss is 25.4 
W/m
2
, then the total heat loss is: 
3196+1016=4212W 
According to the formula Q= CρGΔT, the flow rate is 
 
Loop quantity is 0.3622/0.18=2.012 and the round-off number is 2. 
7.2.5 Check 
A. Check for the flow rate 
 
Floor rate of each loop is within 0.25~0.5m/s and the system can run stably. 
B. Check for the tube length   
When the average tube spacing is 30mm, the required length of the heating pipe per square meter is 
3.5m, length of total coils is 3.5×40=140 and length for each loop is 140/2=70. 
It  can  be  seen  that  the  length  for  each  loop  is  less  than  120m  and  there  it  meets  the  design 
requirement. 
C. Check for the ground average temperature 
tp=tn+9.82×(qx/100) 0.969=20+9.82×(82/100) 0.969=28°C 
Upper Limits and Average Floor Temperature 
7.3 Model Selection 
Heat demand for a single layer: 3196W 
Heat loss for a single layer: 1016W 
Total heat load for a single layer: 4212W 
Total heat load of the building: 8424W 
Capacity of the main unit should be larger than 8424W, so we can select: 
GRS-CQ10Pd/NhG-K OR 
GRS-CQ10Pd/NhG-M