Unit Control 
 
1 Integral Control Concept 
1.1 Control Principle Diagram 
 
1. The outdoor temperature is detected by the sensor installed at fins of the finned heat exchanger, 
which is mainly used to control the initialization steps of the fan and the electrostatic expansion valve 
and also limit the maximum running frequency of the compressor. When this sensor fails, the main board 
will detect it and deliver this error message to the controller and then the unit will fail to start up or shut 
down. 
2. The defroste temperature is detected by the sensor installed at the defrosting pipes of the finned 
heat exchanger, which is mainly used to control defrosting. When this sensor fails at the heating or water 
heating mode, the compressor will stop and this error will be displayed at the controller. When it fails at 
the cooling mode, the compressor continues to run but this error will be displayed at the controller. 
3.  The  discharge  temperature  is  detected  by  the  sensor  installed  at  the  discharge  pipe  of  the 
compressor, which is mainly used for high discharge temperature protection. When this sensor fails, this 
error will be displayed at the controller, all loads except the water pump of the solar system and the 
electric heater of the water tank will stop. Then, the main unit will resume normal running when this error 
is eliminated. 
4. The suction temperature is detected by the sensor installed at the suction pipe of the compressor, 
which is mainly used to control superheating degree. When this sensor fails, this error will be displayed 
at the controller, all loads except the water pump of the solar system and the electric heater of the water