Unit Control 
 
water heating range of the main unit, the water tank heater will start. At any time, only one between the 
auxiliary electric heater and the water tank heater is allowed to run. 
Over-temperature Protection for Water Heating 
When the compressor is running, if it is detected that the leaving water temperature of the auxiliary 
electric  heater  of  the  main  unit  is  higher  than  the  over-temperature  protection  temperature,  the 
compressor will lower its operating frequency until it reaches the minimal operating frequency. At this 
point,  if  it  is  still  detected  that  leaving  water  temperature  is  still  lower  than  the  over-temperature 
protection,  all  loads  except  the  water  pump  of  the  main  unit  and  the  4-way  valve  will  stop. 
Over-temperature  protection  will  exit  when  the  leaving  water  temperature  is  lower  than  the 
over-temperature protection temperature. Then, the main unit will resume normal operation. 
2.3.2 Water Heating by the Solar System 
When the solar water heating system is equipped but temperature difference ( it is the difference of 
solar panel temperature and the actual water tank temperature) for startup is not satisfied, the water 
pump of the solar system will not start. When the temperature difference is satisfied, the water pump will 
start.  However,  when  it  is  detected  that  the  water  tank  temperature  reaches  the  set  point,  or  the 
entering/leaving water temperature difference of the solar panel is too small, then this water pump will 
stop running. 
2.4 Shutdown 
There are three kinds of shutdown conditions: normal shutdown, shutdown with some error, shutdown 
for protection 
Shutdown sequence: for normal shutdown, the compressor lowers its frequency firstly to the minmum 
value, while for shutdown with some error or for protection, the compressor will stop directly.Then, the 
electrostatic expansion valve turns to the maximum opening angle; the fan stops after the compressor 
has stopped; the water pump of the main unit stops after the compressor has stopped; the electrostatic 
expansion valve turns the maximum opening angle to the fixed opening angle. 
During shutdown under the heating and water heating modes, the 4-way valve will be powered off 
after the compressor has stopped. 
For shutdown owing to some error (except the communication error) or protection, the 4-way valve will 
keep the power-on status. 
For shutdown owing to communication between the unit and the wired controller, the 4-way valve will 
be powered off some timer later. 
For  shutdown  with  some  error  or  for  protection,  the  electrostatic  expansion  valve  will  keep  the 
maximum opening angle. 
2.5 Control to the Compressor 
When the unit is controlled by the leaving water temperature, the output frequency of the compressor 
is adjusted by the difference between the actual water temperature and the leaving water temperature 
set point. When the unit is controlled by the room temperature, the output frequency of the compressor is 
adjusted by the difference between the actual room temperature and the room temperature set point. 
2.6 Control to the Fan 
Under the cooling mode, the operating frequency of the fan is adjusted according to pressure at the 
high pressure side. Under the heating or water heating mode, the operating frequency of the fan is 
adjusted  according  to  the  pressure  at  the  low  pressure  side.  During  defrosting,  the  fan  stops  and