Unit Control
[Notes]
This function is allowed only when the unit has just repowered and not turned on. For the unit which
once has been put into operation, this function is unavailable, alerting ―
Wrong operation
‖.
● This function will not be memorized upon power failure.
3.2.4.17 Parameter Setting
[Operation Instructions]
At the commissioning parameter setting page, by touching ―PARAM.‖, it will access to the pages as
shown below.
Page of Commissioning Parameters
At this page, select the desired option and then go to the corresponding page.
After that, by pressing ―OK‖, this setting will be saved and then the unit will run based on this setting;
or by pressing ―Cancel‖, this setting will not be saved and quit.
No
Full Name
Display Name
Range
Default
Remark
1
T-HP max
T-HP max
40~55
104~131
50
/122
2
Cool run time
Cool run time
1~10min
3min
[2-way valve Off]
When ―Cool run time‖ has
expired and temperature
difference keeps at the
standby zone, the unit will
stop.
5min
[2-way valve On]
3
Heat run time
Heat run time
1~10min
3min
[2-way valve Off]
When ―Heat run time‖ has
expired and temperature
difference keeps at the
standby zone, the unit will
stop.
5min
[2-way valve On]
[Notes]
For parameters with different defaults at different conditions, once the current condition changes, the
corresponding default also will change.
● All parameters at this page will be memorized upon power failure.
3.2.5 Viewing
[Operation Instructions]
1. At the menu page, by touching ―
VIEW
‖, the control panel will go to the sub-menu page as shown in