3.4.8 “F0” Indoor Ambient Temperature Sensor Error
Error display: IDU wired controller and IDU receiver light board will display F0
Error judgment condition and method:
Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge the
range of AD value, If the sampling AD value exceeds upper limit and lower limit in 5 seconds continuously, report
the error.
Possible reason:
■Poor contact between ambient temperature sensor and terminal in mainboard interface
■Ambient temperature sensor is abnormal
■Detecting circuit is abnormal
Troubleshooting
3.4.9 “F1” Evaporator Temperature Sensor Error
Error display: IDU wired controller and IDU receiver light board will display F1
Error judgment condition and method:
Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge the
range of AD value, If the sampling AD value exceeds upper limit and lower limit in 5 seconds continuously, report
the error.
Possible reason:
■Poor contact between temperature sensor and terminal in mainboard interface
■Temperature sensor is abnormal
■Detecting circuit is abnormal

Table of Contents

Other manuals for Gree GUD125W/NhA-X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GUD125W/NhA-X and is the answer not in the manual?

Gree GUD125W/NhA-X Specifications

General IconGeneral
BrandGree
ModelGUD125W/NhA-X
CategoryAir Conditioner
LanguageEnglish

Related product manuals