GREE U-Match 5 SERIES UNIT SERVICE MANUAL
83
Troubleshooting
3.4.32 “Pc” Driver Current Error
Error display: ODU mainboard, IDU wired controller and IDU receiver light board will display PC
Error judgment condition and method:
After power charging, if offset voltage average is detected to exceed 12.5% of 1.65V in 1s, then it can be
judged that current detection (or current sensor) circuit is faulted. System will shut down for protection.
Possible reason:
Current detection (or current sensor) sampling circuit element is abnormal.
■Drive chip compressor current sampling AD terminal is badly welded or short-circuited.
Troubleshooting
PC Current detection
(or current sensor)
c
ircuit error
Replace the drive
board.