Service Manual
35
Installation and Maintenance
 Safety Precaution:
1. Must follow the electric safety regulations when installing the unit.
2.  If  the  supply  cord  is  damaged,  it  must  be  replaced  by  the 
manufacturer or  its  service  agent or a similarly qualified person in 
order to avoid a hazard.
3. According  to  the  local  safety  regulations,  use  qualified  power 
supply circuit and air switch.
4. A air  switch  having a contact  separation  of  at  least  3mm in all 
poles should be xed in xed wiring.
5. The appliance shall be installed in accordance with national wiring 
regulation.
6. The air  switch must have  the functions of  magnetic tripping and 
heat tripping in  order  to  prevent  short circuit or  overload.  Please 
install the air switch with suitable capacity according to the sheet 
below.
7. Make sure the power supply matches with the requirement of air 
conditioner.Unstable power supply or  incorrect wiring may  result in 
electric shock, re hazard or malfunction. Please install proper power 
supply cables before using the air conditioner.
8.Properly connect the live wire, neutral wire and grounding wire of 
power socket.
9.Be sure  to cut off the power supply before  proceeding  any work 
related to electric safety.
10.Do not put through the power before nishing installation.
11. To be in compliance with EN 61000-3-11, impedance value of 
power-supply system  connected  to  product  must be  less  than  or 
equal to  the  allowable  maximum  value  of  |Zsys|  in  the  following 
sheet:
Before  connecting  the  product  to  public  power  network,  please 
consult your local  power  upply  authority  to  ensure  that  the  power 
network has met the above requirements. 
No requirement for the unlisted product’s impedance value of power-
supply system.
 
Grounding Requirement:
1. The  air  conditioner  is  first  class  electric  appliance.  It  must 
be  properly  grounded  with  specialized  grounding  device  by  a 
professional. Please make sure  it  is  always  grounded  effectively, 
otherwise it may cause electric shock. 
2. The yellow-green wire in air conditioner is grounding wire, which 
can't be used for other purposes. 
3. The grounding  resistance  should  comply  with  national  electric 
safety regulations. 
4.Including an  air  switch  with  suitable  capacity,  please note  the 
following table. Air switch should be included magnet buckle and 
heating buckle function, it can protect the circuit-short and overload. 
(Caution: please do not use the fuse only for protect the circuit)
8.2 Installation Parts-checking 
8.3 Selection of Installation Location
8.4 Requirements for electric connection 
Basic Requirement:
Installing the unit in the following places may cause 
malfunction. If it is unavoidable, please consult the local dealer:
1.The place with strong heat sources, vapors, flammable or 
explosive gas, or volatile objects spread in the air.
2.The  place  with  high-frequency  devices  (such  as  welding 
machine, medical equipment).
3.The place near coast area.
4.The place with oil or fumes in the air. 
5.The place with sulfureted gas.
6.Other places with special circumstances.
Indoor Unit:
1. Avoid installing the indoor unit in a place where generated or 
leaked inammable gas will stay.
2. Avoid installing the indoor unit in a moist place or in a place 
where oil may be splashed on the unit.
3. Select a location where outlet air may reach each corner of 
the room.
4.  Select  a  location  where  connection  pipe  can  be led  to 
outdoor conveniently.
5. Select a location where air inlet and outlet won't be blocked.
6. Select a location with least affection of outdoor air.
7. Select a location with rm and at oor.
8. Retain sufcient space for maintenance and installation.
9. Ensure the installation meets the requirement of installation 
dimension diagram.
10.Keep it away from uorescent lamp.
Outdoor Unit:
1. Select a location where the noise and outow air emitted by 
the outdoor unit will not affect neighborhood.
2. The location should be well ventilated and dry, in which the 
outdoor unit won't  be  exposed  directly  to sunlight  or  strong 
wind. 
3. The  location  should  be  able  to  withstand  the  weight  of 
outdoor unit.
4. Make  sure  that  the  installation  follows  the  requirement  of 
installation dimension diagram.
5. Select a location  which is out  of reach for  children and far 
away from  animals or plants. If it  is unavoidable, please add 
fence for safety purpose.
6. The  height difference between indoor unit and outdoor  unit 
should be within 5m. The length of connection pipe should be 
within 10m.  
No. Name No. Name
1 Indoor unit 7 Sealing gum
2 Outdoor unit 8 Wrapping tape
3 Connection pipe 9
Support of outdoor 
unit
4 Drainage pipe 10 Fixing screw
5
Connecting 
cable(power cord)
11
Drainage plug(cooling 
and heating unit)
6 Wall pipe 12
Owner’s manual, 
remote controller
1.Please contact the local agent for installation.
2.Don't use unqualied power cord.
Note:
models
max |Zsys|   unit:ohms
GVA48AL-M3NNC7A
GVA55AL-M3NNC7A
GVA24AL-K3NNC7A
0.082
0.079
0.036