Service Manual
37
Installation and Maintenance
Fig.11
power 
connection 
wire
cable-cross 
hole
Outdoor unit connection
black
POWER
N
N
L
L
32N(1)
blue bluebrown
brown
yellow-
green
yellow-
green
24K:
48/55K
Outdoor unit connection
L1 L2 L3 N
brown
violet blueblack
yellow-
green
Fig.12
3. Adjust the position of upper and lower adjusting bafe; 
clamp  the  connection  pipe  and  drain  pipe  as  firm  as 
possible.
4. Tighten the screws.
All wires of indoor unit and outdoor unit should be connected 
by a professional. 
1.If the length of power connection wire is insufcient, please 
contact the supplier for a new one. Avoid extending the wire 
by yourself.  
2.For  the  air  conditioner  with  plug,  the  plug  should  be 
reachable after nishing installation.
3.For the air conditioner  without plug, an  air switch must  be 
installed in the line. The air  switch should be all-pole parting 
and the contact parting distance should be more than 3mm.   
Note:
 
Step seven: bind up pipe
1. Bind up the connection pipe, power cord and drain hose with 
the band.(As show in Fig.13)
2.Reserve a  certain  length of drain hose  and  power  cord for 
installation  when  binding  them.  When  binding  to  a  certain 
degree, separate the indoor power and then separate the drain 
hose.(As show in Fig.14)
3. Bind them evenly.
4. The liquid pipe and gas pipe should be bound separately at 
the end.
Step Eight: place the indoor unit
1.Put the bound  pipes  in  the  wall  pipe  and  then  make  them 
pass through the wall hole.
2. Stuff the gap between pipes and wall hole with sealing gum.
(As show in Fig.15)
3. Fix the wall pipe.
4.Check if the indoor unit is installed rmly.
1.The power cord and control wire can't be crossed or winding.
2.The drain hose should be bound at the bottom.
Do  not  bend  the  drain  hose  too  excessively  in  order  to 
prevent blocking.
indoor unit
gas pipe
Fig.13
Fig.14
Fig.15
Note: 
Note:
2. Remove  the wire clip;  connect  the power connection  wire 
to the wiring terminal according to the color; tighten the screw 
and then x the power supply wire,power connection wire with 
wire clip.(As show in Fig.12)
(1) Take  sufficient protective  measures  when  installing  the 
outdoor unit.
(2) Make sure the support can withstand at least four times the 
unit weight.
(3) The outdoor unit should be installed at least 3cm above the 
oor in order to install drain joint.(As show in Fig.18)
(4)  For  the  unit  with  cooling  capacity  of  2300W~5000W, 6 
expansion screws are needed; for the unit with cooling capacity 
of 6000W~8000W, 8  expansion  screws  are  needed; for  the 
unit with  cooling capacity of 10000W~16000W, 10  expansion 
screws are needed.
Note:
8.6 Installation of Outdoor Unit
1. Fix the Support of Outdoor Unit(select it according to the 
actual installation situation)
(1) Select installation location according to the house structure.
(2) Fix the support of outdoor unit on the selected location with 
expansion screws.
Fig.18
Fig.19
chassis
outdoor drain joint
drain hose
drain vent
at least 3cm above the floor