Service Manual
42
Installation and Maintenance
8
High discharge 
temperature 
protection of 
compressor
E4
During cooling and drying 
operation, compressor and 
ODU fan motor stop while 
IDU fan motor operates. 
During heating operation, 
all loads stop.
1. The system is abnormal. (e.g.: 
blockage, etc)
Refer to Malfunction 
Detection Flowchart
2. Abnormal rotation speed of outdoor 
motor (cooling );
3. Abnormal outdoor air intake (cooling);
4. System is normal, but the compressor 
discharge temperature sensor is broken 
or poorly contacted (Please check it 
by referring to the resistance table for 
temperature sensor).
9
Overcurrent 
protection
E5
During cooling and drying 
operation, compressor and 
ODU fan motor stop while 
IDU fan motor operates. 
During heating operation, 
all loads stop.
1. Unstable supply voltage. Normal 
uctuation shall be within 10% of the 
rated voltage on the nameplate;
Refer to Malfunction 
Detection Flowchart
2. Supply voltage is too low and load is 
too high;
3. Measure the current of live wire on 
mainboard. If the current isn’t higher than 
the overcurrent protection value, please 
check the mainboard;
4. The indoor and outdoor heat 
exchangers are too dirty, or the air inlet 
and air outlet are blocked;
5. The fan speed of fan motor is too low 
or the fan motor doesn’t run;
6. The compressor is not running 
normally. There is abnormal sound, oil 
leakage or the temperature of the shell is 
too high, etc;
7. There’s blockage in the system (lth 
blockage, ice blockage, greasy blockage 
or valve hasn’t been opened completely
)
.
10
Communication 
malfunction
E6
During cooling and drying 
operation, compressor 
and outdoor fan stop while 
indoor fan operates. During 
heating operation, all loads 
stop.
See 9.2 (Communication malfunction)
Refer to maintenance 
owchart
11
Overload
malfunction
E8 The entire unit stops.
1. Indoor and outdoor heat exchanger is 
too dirty?
Or air inlet/outlet is blocked?
2. Fan motor is not working. Abnormal 
fan speed; fan speed is too low or the fan 
doesnt run.
3. Compressor operates normally or not? 
Is there any abnormal noise or oil leak? 
Casing is too hot?
4. System is blocked inside? (Dirt 
blockage? Ice blockage?
Oil blockage? Y-valve is not fully open?)
5. Main board temperature sensor detects 
wrongly.
Refer to Malfunction 
Detection Flowchart
12
In defect of
refrigerant
F0
The Dual-8 Code Display 
will show
F0  and the complete unit 
stops.
1. In defect of refrigerant;
2. Indoor evaporator temperature sensor 
works abnormally;
3. The unit has been plugged up 
somewhere.
Refer to Malfunction 
Detection Flowchart