Service Manual
50
Installation and Maintenance
7. High temperature and overload protection (AP1 below means control board of outdoor unit) E8
● If the outdoor ambient temperature is in normal range;
● If the indoor and outdoor fan are running normally;
● If the radiating environment of indoor and outdoor unit is good.
Malfunction diagnosis process:
Start
If the outdoor ambient temperature is 
higher than 53°C?
is good?
If the indoor and outdoor fan are 
running normally?
Replace outdoor 
mainboard
Connect normally?
Adjust the 
connection
Replace fan
capacitor
Replace motor
Fan capacitor is broken?
Motor is broken?
Replace mainboard
Improve the radiating environment of 
unit (clean the heat exchanger and 
remove surrounding obstacles)
Normal protection, please use it 
after improving the outdoor ambient 
temperature
Unit restarts 
normally
Unit restarts 
normally
End
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No