10
Technical Information
Service Manual
2.2 Capacity Variation Ratio According to Temperature
2. Specications
2.3 Cooling and Heating Data Sheet in Rated Frequency
Instruction:
T1: Inlet and outlet pipe temperature of evaporator
T2: Inlet and outlet pipe temperature of condenser
P: Pressure at the side of big valve
Connection pipe length: 5 m.
Cooling:
Outdoor temp.(°C)
Capacity ratio (%)
Outdoor temp.(°C)
Capacity ratio (%)
0
20
40
60
80
100
120
140
-10 -5-7 0510 15 20 2524
Condition Heating
Indoor: DB20°C
Indoor air flow: Super High
Pipe length: 5m
0
20
40
60
80
100
120
140
15 2018 25 30 35 40 45 50 5552
Condition Cooling
Indoor: DB27°C WB19°C
Indoor air flow: Super High
Pipe length: 5m
Heating:
Cooling:
Rated cooling condition(°C) (DB/WB)
Model
Pressure of gas pipe connecting
indoor and outdoor unit
Inlet and outlet pipe temperature of
heat exchanger
Fan speed of
indoor unit
Fan speed of
outdoor unit
Indoor Outdoor P (MPa) T1 (°C) T2 (°C)
27/19 35/24 24K / 36K 0.4 ~ 0.6
in: 9
out: 12
in: 80
out: 36
Super High High
Heating:
Rated cooling condition(°C) (DB/WB)
Model
Pressure of gas pipe connecting
indoor and outdoor unit
Inlet and outlet pipe temperature of
heat exchanger
Fan speed of
indoor unit
Fan speed of
outdoor unit
Indoor Outdoor P (MPa) T1 (°C) T2 (°C)
20/- 7/6 24K / 36K 1.6 ~ 1.8
in: 80
out: 35
in: 2
out: 4
Super High High