31
Technical Information
Service Manual
1. Summary
Temperature parameter
Indoor set temperature (Tpreset)
Indoor ambient temperature (Tamb.)
Inner tube temperature of indoor evaporator (Ttube)
2. Introduction of basic mode function
Once the compressor is energized, there should be a minimum
interval of 3 mins between two start-ups.
If the unit is with memory function and is off before power failure,
the compressor can be restarted without an interval of 3 mins;
if the unit is on before power failure, the compressor will be
restarted with an interval of 3 mins.
Once compressor is started, it won’t stop within 6 mins according
to the change of room temp.
(1) Auto mode
Operation condition and process
Under auto mode, the system will automatically select operation
mode (cooling, dry, heating and fan) according to indoor ambient
temperature.
When Tamb. > 26°C, the system operates under cooling
mode; Ex-factory set temperature is 26°C.
When 20°C Tamb. 26°C, the system operates under
drying mode; Ex-factory set temperature is 24°C.
Heat pump unit: when Tamb. < 20°C, the system operates
under heating mode; Ex-factory set temperature is 20°C.
Cooling only unit: when Tamb. < 20°C, the system operates
under fan mode; Ex-factory set temperature is 20°C.
Protection function is same as that under cooling, drying and
heating mode. (See function protection of this section)
(2) Cooling mode
Operation condition and process
When Tamb. Tset+1°C, the system operates under cooling
mode. In this case, the compressor and the ODU fan motor
operate, and the IDU fan motor operates at set speed.
When Tset-1°C < Tamb. < Tset+1°C, the system will maintain
its previous operation status.
When Tamb. Tset-1°C, the compressor and the ODU fan
motor stop, while the IDU fan motor operates at set speed.
In cooling mode, the 4-way valve is de-energized (4-way valve is
not available for cooling only unit). Temperature setting range is
16°C ~ 30°C.
Protection function (See function protection of this section)
Tpreset +1 ˚C
Tpreset –1 ˚C
Compressor
Outdoor fan motor
Indoor fan motor
Indicates operation Indicates stop
Graphic instruction: (Same as below)
Tamb.
Stop cooling
Start cooling
Original operating status
6 min. 3 min. 6 min.
Set fan speed
(3) Drying mode
Operation condition and process
When Tamb. > Tset+2°C, the system starts drying and
cooling. In this case, the compressor and the ODU fan motor
operate, and the IDU fan motor operates at low speed.
When Tset-2°C Tamb. Tset+2°C, the compressor and the
ODU fan motor operate for 6 mins and stop for 4 mins in cycle;
the IDU fan motor operates at low speed.
When Tamb. < Tset-2°C, the compressor and the ODU fan
motor stop, while the IDU fan motor runs at low speed.
In drying mode, the 4-way valve is de-energized (4-way valve is
not available for cooling only unit); Temperature setting range is
16°C~30°C. Fan speed can’t be adjusted.
Protection functions (See function protection of this section)
T
preset
T
amb.
+2
T
preset-
2
Cooling
Drying
Stop
6 min
6min.
4min.
4min.
Compressor
Low speed
Outdoor fan motor
Indoor fan motor
(4) Heating mode(heating mode is not available for cooling
only uni)
Operation condition and process
When Tamb. Tset-1°C, the system starts heating operation.
In this case, the 4-way valve is energized. The compressor and
the ODU fan motor operates simultaneously; The IDU fan motor
will be started up after delayed for a period of time to make sure
the air conditioner won’t blow out cold wind.
When Tpreset-1°C < Tamb. < Tpreset+1°C, the system keeps
previous operation status.
When Tamb. Tpreset+1°C, the compressor and the ODU
fan motor stop. The 4-way valve is energized all the time. The
6.5 Description of Each Control Operation