Super Free Match 
Service Manual 
 
MAINTENANCE 
126 
Running mode conflicts 
  
E7 E7 
Communication error 
  
E6 
E6  
indoor 
unit address
 
Communication error between the main 
board and driving board 
  
 P6 
Communication error between the main 
board and testing board 
  
 CE 
Gas sensor error of indoor unit   
  
 Fn 
Humidity sensor error of indoor unit   
  
 L1 
Water full error of indoor unit   
  
E9 E9 
Jumper terminal error of indoor unit 
  
C5 C5 
Phase lack of power supply 
  
 dJ 
Fan motor error of outdoor unit 
  
 L3 
Refrigerant recovery mode 
  
Fo Fo 
  BU module 
Indicating LED flashing times 
Errors 
Yellow LED  Green LED Red LED 
Indoor unit 
error code 
Outdoor unit error code
BU 1 is connected 
Flash 1 time 
   
BU 2 is connected 
Flash 2 times 
   
BU 3 is connected 
Flash 3 times 
   
Indoor unit A is connected   
Flash 1 time 
   
Indoor unit B is connected   
Flash 2 times
   
Indoor unit C is connected   
Flash 3 times
   
Indoor unit D is connected   
Flash 4 times
   
Indoor unit E is connected   
Flash 5 times
   
Indoor unit A gas tube 
temperature sensor error 
 
Flash 1 time 
b7  b7 indoor unit address
Indoor unit A liquid tube 
temperature sensor error 
 
Flash 2 times
b5  b5 indoor unit address
Indoor unit B gas tube 
temperature sensor error 
 
Flash 3 times
b7  b7 indoor unit address
Indoor unit B liquid tube 
temperature sensor error 
 
Flash 4 times
b5  b5 indoor unit address
Indoor unit C gas tube 
temperature sensor error 
 
Flash 5 times
b7  b7 indoor unit address
Indoor unit C liquid tube 
temperature sensor error 
 
Flash 6 times
b5  b5 indoor unit address
Indoor unit D gas tube 
temperature sensor error 
 
Flash 7 time 
b7  b7 indoor unit address
Indoor unit D liquid tube 
temperature sensor error 
 
Flash 8 times
b5  b5 indoor unit address
Indoor unit E gas tube 
temperature sensor error 
 
Flash 9 time 
b7  b7 indoor unit address
Indoor unit E liquid tube 
temperature sensor error 
 
Flash 10 times
b5  b5 indoor unit address