5
Technical Information
Service Manual
2.4 Cooling and Heating Data Sheet in Rated Frequency
Rated cooling
condition(°C)
(DB/WB)
Model
Pressure of gas pipe
connecting indoor and
outdoor unit
Inlet and outlet pipe
temperature of heat
exchanger
Fan speed of
indoor unit
Fan speed of
outdoor unit
Indoor Outdoor P (MPa) T1 (°C) T2 (°C)
27/19 35/24 12K 0.9 to 1.1 12 to 14 75 to 37 Super High High
Rated heating
condition(°C)
(DB/WB)
Model
Pressure of gas pipe
connecting indoor and
outdoor unit
Inlet and outlet pipe
temperature of heat
exchanger
Fan speed of
indoor unit
Fan speed of
outdoor unit
Indoor Outdoor P (MPa) T1 (°C) T2 (°C)
20/- 7/6 12K 2.8 to 3.0 70 to 35 2 to 4 Super High High
Instruction:
T1: Inlet and outlet pipe temperature of evaporator
T2: Inlet and outlet pipe temperature of condenser
P: Pressure at the side of big valve
Connection pipe length: 5m.
Cooling:
Heating:
2.5 Noise Curve
Outdoor side noise when blowing
Compressor frequency(Hz)
35
40
45
50
55
60
65
70
75
Noise dB(A)
20 30 40 50 60 70 80 90
25
30
33
20
36
39
42
45
Noise dB(A)
H
SHM LMLMHSL
Indoor fan motor rotating speed
Indoor side noise