BACnet Gateway Kit for Central Air Conditioners
29
24 Water tank mode(setting)
WaterTankModeCommand_XX_
YYY_ZZ
MV(19)+YYY*8192+ZZ*64+2 MV
25
Double-Tube supply Water
Temp
DoubleTubeSupplyWaterTemp_XX_
YYY_ZZ
AI(0)+YYY*8192+ZZ*64+2 AI
26
Floor Heating supply
Water Setting Temp.
FloorHeatingSupplyWater
SettingTemp_XX_YYY_ZZ
AV(2)+YYY*8192+ZZ*64+2 AV
27 Disinfecting Disinfecting_XX_YYY_ZZ BI(3)+YYY*8192+ZZ*64+2 BI
28 Floor heat power FloorHeatPower_XX_YYY_ZZ BI(3)+YYY*8192+ZZ*64+3 BI
29
Water tank control
shielding code(setting)
WaterTankControlShieldingCodeCom
mand_XX_YYY_ZZ
MV(19)+YYY*8192+ZZ*64+3 MV
Parameters of GMV Outdoor Units
30
Outdoor unit general error
mark
OutdoorUnitErrorMark_XX_YYY_ZZ BI(3)+YYY*8192+ZZ*64+4 BI
31 Outdoor unit error code OutdoorUnitErrorCode_XX_YYY_ZZ MI(13)+YYY*8192+ZZ*64+4 MI
32
Outdoor environment
temp
OutdoorEnvironmentTemp_XX_YYY_
ZZ
AI(0)+YYY*8192+ZZ*64+3 AI
33
Complete machine
compressor state
CompleteMachineCompressorState_
XX_YYY_ZZ
BI(3)+YYY*8192+ZZ*64+5 BI
Table 3.2.2
Parameter
number
Instance Number Present_Value Units
Min_
Pres_
Value
Max_
Pres_
Value
Resolution
Parameters of GMV Indoor Units
1 YYY*8192+ZZ*64+1 0:without, 1:with
2 YYY*8192+ZZ*64+1 see Alarm codes
3 YYY*8192+ZZ*64+1 -20~100 -20 100 1
4 YYY*8192+ZZ*64+1 16~30
5 YYY*8192+ZZ*64+2
1- Cool, 2- Dehumidify,3- Fan,4-
Heat; Others-0 means nothing, used
insignicance symbol to express, like
"--";
6 YYY*8192+ZZ*64+1
1- Cool,2- Dehumidify,3- Fan,4-
Heat;Others:0 means nothing, used
insignicance symbol to express, like
"--";
7 YYY*8192+ZZ*64+2 0:Off,1:On
8 YYY*8192+ZZ*64+1 0:Off,1:On
9 YYY*8192+ZZ*64+3
0- Auto fan speed,1- Low fan
speed,2- Middle fan speed,3- High
fan speed;
10 YYY*8192+ZZ*64+2
1- Low fan speed,2- Middle fan
speed,3- High fan speed;
11 YYY*8192+ZZ*64+1 0:Off,1:On