BACnet Gateway Kit for Central Air Conditioners
30
12 YYY*8192+ZZ*64+2 0:Off,1:On
13 YYY*8192+ZZ*64+3 0:Without shield ,1:Shield
14 YYY*8192+ZZ*64+4 0:Without shield ,1:Shield
15 YYY*8192+ZZ*64+5 0:Without shield ,1:Shield
16 YYY*8192+ZZ*64+6 0:Without shield ,1:Shield
Specic Parameters of GMV Water Heater
17 YYY*8192+ZZ*64+1 0:without, 1:with
18 YYY*8192+ZZ*64+1 see Alarm codes
19 YYY*8192+ZZ*64+1
1) Hot Water, Night, Reserve
modes:35 ~58 (the upper
limit can be adjusted to 65 );
2) Energy saving mode:35 ~50 ;
3) High temp sterilization mode:65
~70 ;
1
20 YYY*8192+ZZ*64+1
1) Hot Water, Night, Reserve
modes:35 ~58 (the upper
limit can be adjusted to 65 );
2) Energy saving mode:35 ~50 ;
3) High temp sterilization mode:65
~70 ;
21 YYY*8192+ZZ*64+2
7-off,8-heat preservation and
standby,9-heating water
22 YYY*8192+ZZ*64+1
7-off,8-heat preservation and
standby,9-heating water
23 YYY*8192+ZZ*64+3
1-energy saving mode mode,2-
reservation mode mode,3-night
mode,4-hot water mode
24 YYY*8192+ZZ*64+2
1-energy saving mode mode,2-
reservation mode mode,3-night
mode,4-hot water mode
25 YYY*8192+ZZ*64+2 -127~255 -127 255 1
26 YYY*8192+ZZ*64+2 30~52
27 YYY*8192+ZZ*64+2 0:No,1:Yes
28 YYY*8192+ZZ*64+3 0:off, 1:on
29 YYY*8192+ZZ*64+3 see shield mark codes
Parameters of GMV Outdoor Units
30 YYY*8192+ZZ*64+4 0:without, 1:with
31 YYY*8192+ZZ*64+4 see Alarm codes
32 YYY*8192+ZZ*64+3 -127~255 -127 255 1
33 YYY*8192+ZZ*64+5 0:off, 1:on