GREE Duct type Ducted Type Split Air-Conditioner Units
62
(1) If you choose 01,the indoor motor will adjust static pressure of the blast pipe automatically
when start-up every time.Here is the way to enter P67.
(2) Long press FUNCTION button for 5s and the temperature zone displays “C00”; press MODE
button for three times in 3s;long press FUNCTION button for another 5s to enter the interface of
setting wired controller parameters. “P00” is displayed in temperature zone.
(3) Press “▲” or “▼” button to select parameter code. Press MODE button to enter parameter
setting. At that time, parameter value is blinking. Press ▲” or “▼” button to adjust the
parameter value and press ENTER/CANCEL button to finish setting.
(4) Press ENTER/CANCEL button to return to last step until exists setting parameters.
The parameter setting list is as following:
Parameter code Parameter name Parameter range Default value
P67 Select the way of adjusting static pressure
00: manually
01:automatically
00
3.3.3 External Static Pressure Reading
If you want to know the exact external static pressure,you can set P67 to 01,restart the
machine,after about 2 minutes,enter C24 to read the exact ESP.
(1) Long press FUNCTION button for 5s and the temperature zone displays “C00”; press MODE
button for three times in 3s.
(2) Press “▲” or “▼” button to C24,there you can read the exact ESP.
3.4 Installation Notice
(1) The unit shall be installed by the professional personnel according to this installation instruction
to ensure proper use.
(2) Please contact the local Gree appointed service center before installation. Any
malfunctioncaused by the unit that is not installed by the Gree appointed service center would
probably not be dealt with on time because of the inconvenience of the business contact.
(3) It should be guided under the professional personnel when the air conditioner unit is moved to
other place.