82
1.5.6 Reset Factory Setting
(1) Reset defaulted factory setting 1 (clear all settings):
Long press “SW1 + SW4” button for over 10s in the main module, the nixie tube will display “oC” for
3s, the main board will remove all settings, including IP address of indoor and outdoor unit.
(2) Reset defaulted setting 2 (clear all settings other than project debugging status):
Long press “SW2 + SW4” for over 10s in the main module, the nixie tube will display “oC” for 5s, the
main board will remove all settints, including IP address of indoor and outdoor unit, but completion label
for project debugging and the memory of indoor and outdoor unit quantity shall be kept.
(3) Reset defaulted setting 3 (clear function setting of outdoor unit only):
Long press “SW3 + SW4” for over 10s in the main module, the nixie tube will display “oC” for 7s,
then clear all function settings of the system, but project code of indoor and outsoor unit, the memory of
indoor and outdoor unit quantity and completion label for project debugging shall be kept.
2 Troubleshooting
Display
Content
Display
Content
Display
Content
L0
Malfunction of
L9
Wrong number of indoor unit
for one-to-more indoor unit
d8
Malfunction of water
L1
Indoor fan
LA
Wrong series for
d9 Malfunction of jumper cap
L2 E-heater protection LH
Alarming due to bad air
dA
Abnormal address for
L3
Water overflow
protection
LC
The indoor unit model can’t
match with outdoor unit
dH
Abnormal PCB for wired
controller
L4
Power supply
of wired controller is
d1 Poor indoor PCB dC
Abnormal code-dialing
setting of capacity
L5
Freeze prevention
d3
Malfunction of ambient
dL
Malfunction of air exhause
L6 Mode shock d4
Malfunction of entry tube
dE
Malfunction of indoor C0
2
L7 No main indoor unit d6
Malfunction of exit tube
C0 Communication malfunction
L8
Insufficient power
d7
Malfunction of humidity
AJ Clean alarming for filter
db Special code: engineering debugging code
Display
Content
Display
Content
Display
Content
E0
Malfunction of
E1 High pressure protection E2
Low-temperature
E3
Low pressure
protection
E4
Discharge high temperature
protection for compressor
EC
Loose protection for
discharge temperature
F0
Poor main board of
F1
Malfunction of high pressure
F3
Malfunction of low
F5
Malfunction of
discharge
temperature sensor
J0 Other module protection J1
Overcurrent protection for
compressor 1
J7
Air-mixing protection
J8
High pressure ration
J9
Low pressure ratio