GREE Duct type Ducted Type Split Air-Conditioner Units
75
Inspection record before debugging
Type
No.
Inspection items
Reference value
Pass or not
Examiner
Electrical
system
inspection
13
Is wiring method of power cable
correct? Is the wiring terminal firm?
Make sure the wiring is
correct and firm.
14
Is the appearance of power cable in
good condition without exposure?
The appearance is in good
condition, exposure is not
allowed.
15
Is the power capacitance less than
the max power of the unit?
Greater than the max power
of the unit.
16
Under power outage condition, is
the electrical component inside the
electrical box loose?
Loose is not allowed.
17
Does the IDU and ODU wire
diameter meet unit design
requirement?
Refer to electric installation.
18
Does the circuit breaker and
leakage switch meet unit design
requirement?
Refer to electric installation.
19
Does the supply voltage, phase
sequence and frequence meet unit
design requirement?
Consistent with unit
nameplate, fluctuation range
of voltage is within ±10%.
20
Is the distance between power
cable and TV over 1m?
The distance between power
cable and TV shall be over
1m.
21
Are there strong electromagnetic
interference, dust, acid and alkaline
gas around the unit?
No battery interference, dust,
acid and alkaline gas around
the unit.
Communication
system
inspection
22
Does the communication wire
diameter meet unit design
requirement?
-
23
Is the communication of outdoor
master unit and IDU correct?
Tandem connection.
24
Is the communication connection
between IDU and wired controller
correct?
-
25
Communication cord and power
cord shall not be laied in the same
trunking, lay individually with
inflaming retarding hard PVC pipe,
and the parallel interval between
communication cord and strong wire
shall be over 20cm.
-
IDU installation
inspection
26
Any slope of 1/100 in drain pipe of
IDU?
-
27
Is the lifted height of drain pipe of
IDU below 85cm?
Water pump unit.
28 Is drain pipe of IDU smooth?
-
29
Are there U-shape water loop in
drain pipe of IDU?
-
30
Soft connection in air outlet/inlet of
IDU?
Duct type unit.
31
Air discharge outlet in drain pipe of
IDU?
-

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree UML600H/A-MP and is the answer not in the manual?

Gree UML600H/A-MP Specifications

General IconGeneral
BrandGree
ModelUML600H/A-MP
CategoryAir Conditioner
LanguageEnglish

Related product manuals