Design & Selection
5 Section of FCU
5.1 FCU Type Selection
The air-water fan coil unit is optional for Versati units
5.2 Matching of Capacity
Load of the FCU is better to be between 70%~120% of the Versati unit.
Notes:
When load of the FCU is too small, the unit would start/stop frequently, which is adverse for oil return.
When load of the FCU is too large, the unit would always run under high frequency, which is unhelpful for
energy conservation.
Type
Air Volume
(m
3
/h)
Cooling
Capacity
(kW)
Heating
Capacity
(kW)
Static
Pressure
(Pa)
Appearance
Wall mounted
type
166~1020 2.1~5.4 3.15~8.5 ——
Concealed
ceiling type
213~2380 1.85~12.8 3.1~21 12, 30
Floor ceiling
type
213~2040 1.9~10.8 2.8~16.2 ——
Cassette type 480~1700 4.5~9 6.8~13.7 ——