8
Design & Selection
6 Selection of the Water Tank
6.1 Specications of the Water Tank
SXVD200LCJ/A-K
220~240V-1Ph-50Hz
A single coil with the electric heater is integrated, used for oor heating system
SXVD300LCJ/A-K
SXVD200LCJ2/A-K
220~240V-1Ph-50Hz
Dual coils with the electric heater are integrated, used for oor heating system and the solar system
SXVD300LCJ2/A-K
SXVD200LCJ/A-M
380~415V-3Ph-50Hz
A single coil with the electric heater is integrated, used for oor heating system
SXVD300LCJ/A-M
SXVD200LCJ2/A-M
380~415V-3Ph-50Hz
Dual coils with the electric heater are integrated, used for oor heating system and the solar system
6�2 Volume Selection of the Water Tank
6.2.1 Selection Based on Water Consumption Per Capita
Building Type Unit Daily Water Consumption (L) Water Temperature (°C)
House Per person, Per day 40~80 60
Villa Per person, Per day 70~110 60
6�2�2 Selection Based on Sanitary Utensils
Utensil Type
Daily Water
Consumption (L)
Water Temperature (°C)
Bathtub, Sprinkler system (with shower) 150 40
Bathtub, Sprinkler system (without shower) 125 40
Shower 70~100 37~40
Wash Basin 3 30
6� 2�3 Selection of the Water Tank
Selection of the water tank should consider the ow rate of the shower head, duration of use per person
and daily water consumption.
Volume of the Water Tank=
t(design temperatuere)-t(entering cold water temperatuere)
t(water tank temperatuere set point)-t(entering cold wa ter temperature)
•consumption
t (design temperature): generally it is 60°C ;
t (entering cold water temperature): it differs for different regions.
t ( water tank temperature set point): it is the target heating temperature of the water tank
α: correction factor
Empirical Values for Volume Correction of the Water Tank
Duration of Use
(min/Person)
Flow Rate of the Shower Head
(L/min)
10 15 20 25 30 40
4 0.48 0.71 0.94 1.18 1.42 1.89
6 0.71 1.06 1.42 1.77 2.12 2.83
8 0.95 1.42 1.89 2.36 2.83 3.77
10 1.18 1.77 2.36 2.95 3.54 4.72
15 1.76 2.65 3.54 4.42 5.31 7.08
Empirical values are worked out under conditions of 80L consumption (per day per person), 8L/min ow rate
of the shower head, and 10 minutes use duration per person.
7 Examples for Model Selection
7�1 General Introduction to the Example Project
For a two-oor house, there is a master room and a both room for each oor and both of
them require oor heating. Other rooms use the heat pump for heating in winter. The master
room covers 28m
2
and the both room covers 12m
2
.