22
Air to Water Heat Pump
Service Manual- Versati Series
DPOUSPM
6) Repeat step 2 to 5 to set other function parameters. Press button or button to return the
main menu.
Table of user function parameter
Code Function description Detail Range
1
Setting temperature selection:
Selection for setting temperature as
room temperature or outflow water
temperature
0: leaving water temperature
1: room temperature
0~1(default: 0)
2 Forced Operation
0: no Forced operation
1: Forced cooling operation
2: Forced heating operation
0~2(default: 0)
3
Celsius/Fahrenheit switching:
Display temperature in Celsius or
Fahrenheit
0:Celsius
1:Fahrenheit
0~1(default: 0)
4 Thermostat control isEnable/disable
0: disable
1: enable
0~1(default: 0)
5 Enable/disable of quick sanitary heating
0: disable
1: enable
0~1(default: 0)
6 Enable/disable of disinfection operation
0: disable
1: enable
0~1(default: 0)
7 Enable/disable of holiday mode
0: disable
1: enable
0~1(default: 0)
8
Setting priority when under cooling
demand and sanitary water heating
demand are required at the same time
0: priority to cooling
1: priority to water tank heating
0~1(default: 0)
9
Setting priority when under heating
demand and sanitary water heating
demand are required at the same time
0: priority to heating
1: priority to water tank heating
0~1(default: 0)
10
Setting status of back-up heater(indoor
unit)
1: use half capacity of Back-up
heater(3kW)
2: use full capacity of Back-up
heater(6kW)
1~2(default:1)