Air to Water Heat Pump
Service Manual- Versati Series
DPOUSPM
11
Setting start date of disinfection
operation
0: Sunday
1: Monday
2: Tuesday
3: Wednesday,
4: Thursday
5: Friday
6: Saturday
0~6(default: 6)
12
Setting start time in 24 hours of
disinfection operation
00-00:00
01-01:00
23-23:00
0~23(default:23)
13
Enable/disable of Metal Base (pedestal)
heater
0: disable
1: enable
0~1(default:1)
14 Tank sensor quantity
1: one
2: two
1~2(default:2)
15 Tank equipment
0: NOT Equipped
1: Equipped
0~1(default: 0)
16 Other thermal equipment
0: NOT Equipped
1: Equipped
0~1(default: 0)
17 FCU equipment
0: NOT Equipped
1: Equipped
0~1(default: 0)
18 Remote air temperature sensor
0: NOT Equipped
1: Equipped
0~1(default: 0)
19 Heating operation level
0: high temperature cycle
1: low temperature cycle
0~1(default:1)
20
Setting turn on temperature of back-up
heater(indoor unit)
/ -20~18
(default: 0 )
21
Setting maximum water tank
temperature heated by heat pump cycle
/ 40~50
(default: 50 )
22
Setting heating temperature of
disinfection operation
/ 40~70
(default: 70 )
23
Setting lower temperature for Weather-
dependent operation
/ -20~5
(default: -15 )
24
Setting upper temperature for Weather-
dependent operation
/ 10~20
(default: 15 )
25
Setting temperature gap from target
temperature of cooling operation
/ 2~10
(default: 5 )
26
Setting temperature gap from target
temperature of heating operation
/ 2~10
(default: 5 )
27
Setting temperature gap from target
temperature of sanitary heating
operation
/ 2~8
(default: 3 )
3.2.3.4 Function Set-up Description
Function code 1: Setting temperature selection
7KHXQLWFDQRSHUDWHDFFRUGLQJWRDLUWHPSHUDWXUHRURXWÀRZZDWHUWHPSHUDWXUH7KHDLUWHPSHUDWXUHRU
RXWÀRZZDWHUWHPSHUDWXUHFDQEHVHOHFWHGDVVHWWLQJWHPSHUDWXUH
Note: Air temperature as setting temperature is ONLY available when Remote Air Sensor Connection is
enabled and Function Code 18 is set as 01.
Function code 2:Forced operation
Forced Operation includes forced cooling and forced heating operation:
Forced cooling operation should be performed when additional refrigerant charge is required.
To charge the refrigerant, the unit must run in Cool mode.
)RUFHGFRROLQJVKRXOGEHSHUIRUPHGXSRQWKH¿UVWUXQWHVWUXQDQGZKHQRXWGRRUWHPSHUDWXUHLVORZHUWKDQ