27
Air to Water Heat Pump
Service Manual- Versati Series
DPOUSPM
The table of user function parameter
Code Function description Detail Range
1 Setting interval of defrost mode / 30~60minute(default:50)
2 Setting duration of defrost mode / 1~15minute(default:10)
3
Setting enter temperature of preventing freezing
operation
/ 1~5
(default:3 )
4 Setting exit temperature of preventing freezing operation / 6~14
(default:12 )
5
Setting enter temperature of anti-high temperature
operation
/ 55~60
(default:58 )
6
Setting exit temperature of anti-high temperature
operation
/ 40~54
(default:53 )
7 Setting enter temperature of defrost operation / -10~0
(default:-4 )
8 Setting exit temperature of defrost operation / 5~30
(default:15 )
3.2.3.6. Set target temperature
1) Press
button or button to turn on the unit.
2) Press repeatedly button to select one target temperature: room temperature,
RXWÀRZZDWHUWHPSHUDWXUH sanitary water tank temperature, DQGVRODURXWÀRZZDWHUWHPSHUDWXUH
The setting temperature is blinking.