EasyManua.ls Logo

Growatt MID TL3-XH Series - Page 60

Growatt MID TL3-XH Series
63 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5655
MID
17KTL3-XH
MID
20KTL3-XH
MID
25KTL3-XH
MID
30KTL3-XH
Input data (DC)
Recommended Max. PV
power (for module STC)
34000W
40000W
50000W
60000W
Max. DC voltage
1100V
Start voltage
200V
Nominal voltage
600V
MPPT voltage range
160-1000V
No. of MPP trackers
2
3
No. of PV strings per
MPP tracker
2/2
2/2
2/2/2
2/2/2
Max. input current per
MPP tracker
32A/32A
32A/32A
32A/32A/32A
32A/32A/32A
Max. short-circuit
current per MPP tracker
40/40A
Backfeed current to PV
array
0A
DC Battery
Compatible
battery(only)
APX HV Battery
(5kWh~60kWh)
Operating voltage range
600 V ~ 980 V
Max. operating current
25A/25A
Max. discharge power
17000W
20000W
25000W
30000W
Max. charge power
15000W/30000KW
Qutput data (on-grid)
Nominal AC power
17000W
20000W
25000W
30000W
Max. AC apparent
power
18700VA
22000VA
27500VA
30000VA
Nominal AC
voltage/range
230/400V
AC grid frequency/range
50/60 Hz
45~55Hz/55-65 Hz
Max. output current
28.3A
33.3A
41.6A
45.5A
AC inrush current
60A
Max. output fault
current
74.1A
106.7A
Max. output overcurrent
Protection
74.1A
106.7A
Power factor(@nominal
power)
>0.99
Model
Specifications
MID
17KTL3-XH
MID
20KTL3-XH
MID
25KTL3-XH
MID
30KTL3-XH
THDi
<3%
AC grid connection type
3W+N+PE
Efficiency
Max. efficiency
98.00%
Euro-eta
97.50%
Output data (Backup)
Nominal output power
17000W
20000W
25000W
30000W
Max. apparent power
18700VA
22000VA
27500VA
30000VA
Nominal AC output
voltage
230V/400V
Nominal AC output
frequency
50Hz
Max. output current
25.8A
30.3A
37.9A
45.5A
Power factor
0.8 leading to 0.8 lagging
THDv
THDv2%@Rload, THDv5%@RCDload
DCV
300mV AVG
Switch time
<500ms
Protection devices
DC reverse-polarity
protection
YES
DC switch
YES
DC surge protection
YES
Insulation resistance
monitoring
YES
AC surge protection
YES
AC short-circuit
protection
YES
Grid monitoring
YES
Anti-islanding
protection
YES
Residual-current
monitoring unit
YES
String Fuse protection
NO
String monitoring
YES
AFCI protection
YES
Model
Specifications

Related product manuals