8
CAN
Communication protocol
Protocol 51
Protocol 52
.
.
.
.
.
.
Protocol 99
Note: When the battery type set to Li, the setting option 12, 13, 21 will change to display percent.
Note: When the battery type set as LI”, the Maximum charge current can't be modified by the user. When the
communication fail, the inverter will cut off output.
Note: Any questions about communicating with BMS, please consult with Growatt.
3. Communicating with battery BMS in parallel system
If need to use communicate with BMS in a parallel system, you should make sure to connect the BMS
communication cable between the battery and one inverter of the parallel system. Its recommended to connect to
the master inverter of the parallel system.
12
Setting SOC point back to
utility source when selecting
“SBU priority” or “Solar first”
in program 01
Default 50%, 6%~95% Settable
13
Setting SOC point back to
battery mode when selecting
“SBU priority” or “Solar first”
in program 01
Default 95%, 10%~100% Settable
21
Low DC Cut-off SOC.
If self-defined is selected in
program 5, this program can be
set up
Default 20%, 5%~50% Settable

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Growatt SPF 2000TL and is the answer not in the manual?

Growatt SPF 2000TL Specifications

General IconGeneral
ModelSPF 2000TL
CategoryInverter
Rated Power2000W
Output Voltage230VAC
USB PortYes
Operating Temperature-10°C to 50°C
CoolingFan
Frequency50Hz/60Hz
Battery TypeLead-acid or Lithium-ion
CommunicationRS232

Related product manuals