Pos. Description
4 Arrow button for changing control mode.
5
QR code.
Scan the QR code for access to additional product information and
documentation.
6
Temperature mode.
The LED is permanently green when the pump operates. It flashes
green when the pump is waiting for water to cool down.
AUTOADAPT control mode
The pump learns usage patterns throughout the day and ensures hot water is
available only when needed via an external sensor on the supply pipe. During
the first two to three weeks after installation, the pump frequently starts based
on temperature control to ensure immediate comfort until usage pattern has
been learned. The pump will despite usage patterns still provide instant comfort
when it detects demand for hot water.
After 24 hours of inactivity, the pump automatically enters vacation mode and
resumes operation when it detects demand for hot water.
Once a week, the pump runs a 15 minute disinfection cycle. The water heater
must enable that function once a week.
Temperature control mode
Comfort is ensured via an external and internal sensor for more accurate water
temperature measurement. The pump can automatically adjust on/off
temperatures based on the maximum temperature measured in the system. For
example, if the maximum water temperature is measured at 113 °F (45 °C), the
pump switches off at temperatures above 106 °F (41 °C) and switches back on
when the water cools down to below 100 °F (38 °C).
After 24 hours of inactivity, the pump automatically enters vacation mode and
resumes operation when it detects demand for hot water.
Continuous 24/7 control mode
The pump operates continuously 24 hours per day.
15