12. Priority of settings 
You can always set the motor to operation at 
maximum speed or to stop with R100 or Grundfos 
GO. 
If two or more functions are enabled at the same 
time, the motor operates according to the function 
with the highest priority.
Example
If you have set the motor to maximum speed via the 
digital input, the motor control panel, R100 or 
Grundfos GO can only set the motor to "Manual" or 
"Stop".
The priority of the settings appears from the table 
below:
* "Stop" and "Max. speed" settings made with 
R100, Grundfos GO or on the motor control panel 
can be overruled by another operating-mode 
command sent from a bus, for example "Start". If 
the bus communication is interrupted, the motor 
resumes its previous operating mode, for 
example "Stop", selected with R100, Grundfos 
GO or on the motor control panel.
Priority
Start/stop 
button
R100, Grundfos GO or 
control panel on motor
Digital input Bus communication
1 Stop
2 Stop*
3 Manual
4 Maximum speed*
5 Stop
6 Stop
7 Maximum speed
8 Minimum speed
9 Start
10 Maximum speed
11 Minimum speed
12 Minimum speed
13 Start
14 Start