English (GB)
35
10.8 ""Digital inputs/outputs""
Available inputs and outputs depend on the 
functional module fitted in the motor. See section 
15. Identification of functional module.
You can select if the interface is to be used as input 
or output. The output is an open collector and you 
can connect it to e.g. an external relay or controller 
such as a PLC etc.
Fig. 31 Example of configurable digital 
inputs/outputs
To set a digital input/output, make the settings below.
Mode
You can set the digital input/output 3 and 4 to act as 
digital input or digital output.
Function
You can set the digital input/output 3 and 4 to the 
functions stated in the tables below. See also 
sections 10.7 "Digital inputs" and 10.9 "Signal relay" 
(""Relay outputs"").
Possible functions, digital input/output 3
Possible functions, digital input/output 4
Activation delay (only for input)
Select the activation delay (T1).
It is the time between the digital signal and the 
activation of the selected function.
Range: 0-6000 seconds.
Duration timer mode (only for input)
Select the duration timer mode. See fig. 30. 
• ""Not active""
• active with interrupt (mode A)
• active without interrupt (mode B)
• active with after-run (mode C)
Select the duration time (T2). 
It is the time which, together with the mode, 
determines how long the selected function is active.
Range: 0-15,000 seconds.
Fig. 32 Duration timer function of digital inputs
TM06 4463 2315
"Function if input" "Function if output"
• ""Not active""
• ""External stop""
•""Min.""
•""Max.""
• ""External fault""
• ""Alarm resetting""
• Reverse rotation
• ""Predefined 
setpoint digit 2""
• ""Not active""
• ""Ready""
•""Alarm""
• ""Operation""
• ""Warning""
• ""Limit 1 exceeded""
• ""Limit 2 exceeded""
"Function if input" "Function if output"
• ""Not active""
• ""External stop""
•""Min.""
•""Max.""
• ""External fault""
• ""Alarm resetting""
• Reverse rotation
• ""Predefined 
setpoint digit 3""
• ""Not active""
• ""Ready""
• ""Alarm""
• ""Operation""
• ""Warning""
• ""Limit 1 exceeded""
• ""Limit 2 exceeded""
TM06 4949 3415
T input
T input > T1 + T2 T input < T1 + T2
T1 T2
T1 T2
T1 T1 T2T2
T1
T1
T input
T2
Mode C
Mode B
Mode A
Digital
input
T input > T1 + T2
T input < T1 + T2